How to adjust to battery voltage of SPF 5000TL HVM /SPF 3000TL HVM 24/48 on lcd display

How to adjust to battery voltage of off grid inverter on lcd display Procedures: Please note that the method just can be used for several voltage difference between real battery voltage and LCD Display. If the difference is large, maybe board is something wrong. Only connect battery to inverter( Don’t connect inverter to utility, PV …

How to adjust to battery voltage of SPF 5000TL HVM /SPF 3000TL HVM 24/48 on lcd display Read More »

SPF 3500-5000ES 62fault

SPF 3500-5000ES 62fault 62fault means Internal communication error Triggering condition:  It has exceeded 10s(20ms*500)since control board can’t receive the data from other chips like M3 chip on control board, Driving chip from MPPT board, mainboard etc. Testing Method: Restart the inverter, check if 62fault will disappear After restarting it, if it is still not …