Modbus Protocol type for Grid, Hybrid Inverter

Modbus Protocol type for Grid, Hybrid Inverter

1. Applicable for these models below

TL-X/TL-XH/TL-XH US(MIN Type)

TL3-X(MAX、MID、MAC Type)

MAX 1500V、MAX-X LV

MAX250KTL3-X HV

MOD TL3-XH

Storage(MIX Type)

Storage(SPA Type)

Storage(SPH Type)

2. register address meaning

Holding register:

这个是电网电压高于某个值或者低于某个值才会触发降载,与安规有关

grid voltage is higher than a certain value or lower than a certain value before degrading is triggered. It is related to safety regulations.

232 value is 1 means: disable N Line of grid.

Input register:

232, 233 Read real time reactive power

232-65525,233-48496,要把两个寄存器值合并转为16进制数:
65525-0xFFF5,48496-0xBD70,合并就是0xFFF5BD70,按有符号数转换成十进制数为-672400,单位是0.1var,所以实际无功是-67240var

232-65525, 233-48496, you need to combine the two register values and convert them into hexadecimal numbers:
65525-0xFFF5, 48496-0xBD70, the combination is 0xFFF5BD70, converted to decimal number as signed number is -672400, the unit is 0.1var, so the actual reactive power is -67240var

329 Register address

单相功率防逆流控制

-X的机器输出是三相平衡的,如果负载不平衡且使能了单相功率防逆流控制,那逆变器输出功率=三相中负载最小功率*3,所以PV逆变器输出功率会受限

-X’s machine output is three-phase balanced. If the load is unbalanced and single-phase power reverse flow control is enabled, the inverter output power = the minimum load power in the three phases * 3, so the PV inverter output power will be limited.

比如说现场逆变器输出功率足够,防逆流百分比为0,三相负载情况是:1K、2K、3K,单相防逆流控制使能的情况下逆变器输出为:1K、1K、1K;单相防逆流控制不使能的情况下逆变器输出为:2K、2K、2K(输出总功率=负载总功率);

For example, if the inverter output power is sufficient, the anti-backflow percentage is 0, and the three-phase load is: 1K, 2K, 3K, the inverter output is: 1K, 1K, 1K when the single-phase anti-backflow control is enabled; the inverter output is: 2K, 2K, 2K when the single-phase anti-backflow control is disabled (total output power = total load power);

1 thought on “Modbus Protocol type for Grid, Hybrid Inverter”

  1. Hi, very good informations!
    i have the problem to find the registeres for PEX1 on the SPH 10000TL3 BHUP.
    The Registercodes 3250 in your documentation is for TLX and on the Registerdocu 1.24 there is nothing.
    did you know where the right registers are to find? i have a installation with a second meter and the display shows successful the PEX1 Power
    Thank you!