How to solve negative value of power generation on SPF 5000TL HVM

How to solve negative value of power generation on SPF 5000TL HVM

Phenomenon

Reason Analysis

Control board memory data overflow

Solution

You can learn how to upgrade inverter via

https://www.amosplanet.org/how-to-upgrade-off-grid-inverter/

password: open20220621

1. MPPT firmware needs to be upgraded as TMS320F28027_sk002.07_202202180952.bin

MPPT Fireware Download ( Specially for power generation negative value)

Please note when upgrading MPPT , make sure that PV system must be connected, or it can’t be upgraded.

2. Control board firmware needs to be upgraded as F2809_SK001.15_20220218A.bin

Control Firmware Download( Specially for power generation negative value)

3. ISP TOOL Download
4. USB driving program Download
5. Clear Power generation negative value

If client doesn’t want to see negative value of power generation, you can clear it .

Procedures:

Press UP AND DOWN for 3 seconds, then input 309 and recover factory set( power generation value will be cleared as 0 ), power generation value will be caculated from 0.

6. modify power generation value

If you want to keep history power generation value, you can modify the register address value via Modscan32

MODscan32 Download

Operation video

2 thoughts on “How to solve negative value of power generation on SPF 5000TL HVM”

  1. Successfully loaded the MPPT firmware.
    However, after loading the Control board firmware the inverter’s display is corrupted. I’ve power cycled the inverter and uploaded the Control board firmware again. Both times the ISP software shows it to be successful yet the display remains unreadable now. No beeps\sounds come when pressing any buttons on it now. Anyway to recover from this?