MOD 3K-15K TL3-X Troubleshooting
1.Error 200
AFCI Fault, DC current ARC fault
AFCI module will have auto-check when entering into INV state, based on given PWM wave and sample the arc signal, if it is in the normal range, it will go through, if not in given range, fault will occur. After 3 times failed check, it will alarm the fault
2.Error 201
GFCI Module damage
Residual I High, Leakage current GFCI is too high
When power on, GFCI will have auto check, Auto-check signal is given by GPIO24, when auto-check, GFCI average value is lower than 69mA or greater than 6mA, disable GFCI function, but it won’t alarm the fault.
3.Error 202
PV input voltage too high
- If the PV voltage is greater than 1070V for 200ms, an error will be reported
- The PV voltage is less than 1000V for 2s to clear the error
4.Error 203
PV Isolation Low
- If the ISO detection resistance is less than 50KΩ, an error will be reported
- After the error is reported, detect the ISO resistance greater than 70KΩ to clear the fault
5.Error 300
AC V Outrange
You can modify register address value below:
52 register address: Vac Low ( Grid voltage low limit protect ) the value equals voltage*10 like 250*10 =2500
53 register address: Vac High ( Grid voltage high limit protect ) the value equals voltage*10 like 480*10 =4800
64 register address: Grid low voltage limit connect to Grid , the value equals voltage*10 like 250*10 =2500
65 register address: Grid high voltage limit connect to Grid , the value equals voltage*10 like 480*10 =4800
80 register address: Voltage protection for 10 mins , the value equals voltage*10 like 480*10 =4800
6.Error 301
AC reverse
7.Error 302
No AC Connection
- The three-phase line voltage is less than 173.2V
- If the condition 1 is not met, the fault will be cleared after 2s
8.Error 303
PE abnormal
This alarm will be detected when the model T bit bit1 is enabled and there is no grid fault. In the non-inverting state, if the NE voltage difference is less than 70V for 1s, the alarm will continue, and if it is less than 120V for 2s, the alarm will be cleared.
9.Error 304
AC F Outrange
You can modify register address value below:
54 Register address: Fac Low, Grid frequency low limit protect, the value equals voltage*100 like 49*100 =4900
55 Register address: Fac High, Grid High frequency limit protect, the value equals voltage*100 like 52*100 =5200
10.Error 305
Over Load
11.Error 306
CT LN Reversed
12.Error 307
CT COM Fault
13.Error 308
Machine and current transformer pairing timed out
14.Error 400
Abnormal DC component bias voltage
15.Error 401
The DC component of the output voltage is too high
16.Error 402
Output High DCI: The DC component of the output current is too high
17.Error 403
Three-phase current output unbalanced
18.Error 404
Abnormal BUS voltage sampling
19.Error 405
Relay fault
20.Error 406
initialization mode error
21.Error 407
Auto-check fails
22.Error 408
Over temperaturer
23.Error 409
Bus voltage abnormal
24.Error 410
Inconsistent sampling of insulation resistance between DSP and M3
25.Error 411
Internal communication error
26.Error 412
NTC OPEN
Abnormal connection of temperature sensor
27.Error 413
Abnormal IGBT drive
28.Error 414
Memory EEPROM read and write errors
29.Error 415
SPS abnormal
30.Error 416
DC/AC overcurrent protection
31.Error 417
Inconsistent sampling of grid voltage between DSP and M3
32.Error 418
Control board and communication board firmware versions do not match
33.Error 419
Inconsistent sampling of leakage current between DSP and M3
34.Error 420
The leakage current detection module is abnormal
35.Error 421
CPLD module abnormal
35.Error 422
One of PV sampling, positive and negative bus sampling, three-phase AC voltage sampling, GFCI, ISO sampling is triggered