How to solve exporting current limitation issue perfectly on Min series
Some clients want to export absolute 0 power to grid. But in real situation, as communication speed limit, it is difficult to do absolute 0 exporting power.
Method 1
This method is for our engineers, they have the authority to set the value on OSS account.
a. Access OSS account–> After sales O&M–> After-sales Inquiry

b. Click “setting’ icon

c. caculate 123 register address value
Formula: 65536-x*10 = -x % ( -x % is our goal)
For example, we want to import 5% power from grid all the time, you can follow the formula: 65536-5*10= -5%, so you can set register address value 65486 on 123 register address

D. set value on 123 register address